60W Constant Voltage + Constant Current LED Driver

NRCS LOA APPROVED

 

 

apv-12

Application:

LED Lighting
LED Moving Sign

Features

 Constant Voltage + Constant current mode ouput
 Metal housing design with class 1 design
 Built-in active PFC function
 Class 2 power unit
 IP67 / IP65 design for indoor or outdoor installations
 Function options: output adjustable via potentiometer
 3 in 1 dimming (dim-to-off)
 Timer Dimming
 Typical lifetime > 62000 hours
 7 year warranty

HLG-60H series

MODELHLG-60H-15HLG-60H-20HLG-60H-24HLG-60H-30
OUTPUTDC VOLTAGE15V20V24V30V
CONSTANT CURRENT REGION9 ~ 15V12 ~ 20V14.4 ~ 24V18 ~ 30V
RATED CURRENT4A3A2.5A2A
RATED POWER60W60W60W60W
RIPPLE & NOISE (max.)150mVp-p150mVp-p150mVp-p200mVp-p
VOLTAGE ADJ. RANGE - Adjustable forA-Type only (via built-in potentiometer)13.5 ~ 17V17 ~ 22V22 ~ 27V27 ~ 33V
CURRENT ADJ. RANGE - Adjustable forA-Type only (via built-in potentiometer)2.4 ~ 4A1.8 ~ 3A1.5 ~ 2.5A1.2 ~ 2A
VOLTAGE TOLERANCE±2.0%±1.0%±1.0%±1.0%
LINE REGULATION±0.5%±0.5%±0.5%±0.5%
LOAD REGULATION±1.5% ±1.0%±0.5%±0.5%
SET UP TIME500ms,80ms/115VAC 500ms,80ms/230VAC`500ms,80ms/115VAC 500ms,80ms/230VAC500ms,80ms/115VAC 500ms,80ms/230VAC500ms,80ms/115VAC 500ms,80ms/230VAC
HOLD UP TIME (Typ.)16ms / 115VAC, 230VAC16ms / 115VAC, 230VAC16ms / 115VAC, 230VAC16ms / 115VAC, 230VAC
INPUTVOLTAGE RANGE90 ~ 305VAC 127 ~ 431VDC90 ~ 305VAC 127 ~ 431VDC90 ~ 305VAC 127 ~ 431VDC90 ~ 305VAC 127 ~ 431VDC
FREQUENCY RANGE47 ~ 63Hz47 ~ 63Hz47 ~ 63Hz47 ~ 63Hz
POWER FACTOR (Typ.)PF>=0.98/115VAC, PF>=0.95/230VAC, PF>=0.92/277VAC @ full loadPF>=0.98/115VAC, PF>=0.95/230VAC, PF>=0.92/277VAC @ full loadPF>=0.98/115VAC, PF>=0.95/230VAC, PF>=0.92/277VAC @ full loadPF>=0.98/115VAC, PF>=0.95/230VAC, PF>=0.92/277VAC @ full load
TOTAL HARMONIC DISTORTIONTHD< 20% (@>=load 60% / 115VAC,230VAC; @ load>=75% / 277VAC)THD< 20% (@>=load 60% / 115VAC,230VAC; @ load>=75% / 277VAC)THD< 20% (@>=load 60% / 115VAC,230VAC; @ load>=75% / 277VAC)THD< 20% (@>=load 60% / 115VAC,230VAC; @ load>=75% / 277VAC)
EFFICIENCY (Typ.)87.5% 89% 89.5%90%
AC CURRENT (Typ.)0.64A/ 115VAC 0.32A/ 230VAC 0.3A/ 277VAC0.64A/ 115VAC 0.32A/ 230VAC 0.3A/ 277VAC0.64A/ 115VAC 0.32A/ 230VAC 0.3A/ 277VAC0.64A/ 115VAC 0.32A/ 230VAC 0.3A/ 277VAC
INRUSH CURRENT(Typ.)COLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410COLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410COLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410COLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410
MAX. No. of PSUs on 16A
CIRCUIT BREAKER
9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VAC9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VAC9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VAC9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VAC
LEAKAGE CURRENT<0.75mA/ 277VAC<0.75mA/ 277VAC<0.75mA/ 277VAC<0.75mA/ 277VAC
Specs Sheet
untitled-3Download PDF
untitled-3Download PDF
untitled-3Download PDF
untitled-3Download PDF

HLG-60H series

MODELHLG-60H-36HLG-60H-42HLG-60H-48HLG-60H-54
OUTPUTDC VOLTAGE36V42V48V54V
CONSTANT CURRENT REGION21.6 ~ 36V25.2 ~ 42V28.8 ~ 48V32.4 ~ 54V
RATED CURRENT1.7A1.45A1.3A1.15A
RATED POWER61.2W60.9W62.4W62.1W
RIPPLE & NOISE (max.)200mVp-p300mVp-p300mVp-p300mVp-p
VOLTAGE ADJ. RANGE - Adjustable forA-Type only (via built-in potentiometer)33 ~ 40V40 ~ 46V44 ~ 53V49 ~ 58V
CURRENT ADJ. RANGE - Adjustable forA-Type only (via built-in potentiometer)1 ~ 1.7A0.87 ~ 1.45A0.78 ~ 1.3A0.69 ~ 1.15A
VOLTAGE TOLERANCE±1.0%±1.0%±1.0%±1.0%
LINE REGULATION±0.5%±0.5%±0.5%±0.5%
LOAD REGULATION±0.5%±0.5%±0.5%±0.5%
SET UP TIME500ms,80ms/115VAC 500ms,80ms/230VAC500ms,80ms/115VAC 500ms,80ms/230VAC500ms,80ms/115VAC 500ms,80ms/230VAC500ms,80ms/115VAC 500ms,80ms/230VAC
HOLD UP TIME (Typ.)16ms / 115VAC, 230VAC16ms / 115VAC, 230VAC16ms / 115VAC, 230VAC16ms / 115VAC, 230VAC
INPUTVOLTAGE RANGE90 ~ 305VAC 127 ~ 431VDC90 ~ 305VAC 127 ~ 431VDC90 ~ 305VAC 127 ~ 431VDC90 ~ 305VAC 127 ~ 431VDC
FREQUENCY RANGE47 ~ 63Hz47 ~ 63Hz47 ~ 63Hz47 ~ 63Hz
POWER FACTOR (Typ.)PF>=0.98/115VAC, PF>=0.95/230VAC, PF>=0.92/277VAC @ full loadPF>=0.98/115VAC, PF>=0.95/230VAC, PF>=0.92/277VAC @ full loadPF>=0.98/115VAC, PF>=0.95/230VAC, PF>=0.92/277VAC @ full loadPF>=0.98/115VAC, PF>=0.95/230VAC, PF>=0.92/277VAC @ full load
TOTAL HARMONIC DISTORTIONTHD< 20% (@>=load 60% / 115VAC,230VAC; @ load>=75% / 277VAC)THD< 20% (@>=load 60% / 115VAC,230VAC; @ load>=75% / 277VAC)THD< 20% (@>=load 60% / 115VAC,230VAC; @ load>=75% / 277VAC)THD< 20% (@>=load 60% / 115VAC,230VAC; @ load>=75% / 277VAC)
EFFICIENCY (Typ.)90% 90% 90.5%90.5%
AC CURRENT (Typ.)0.64A/ 115VAC 0.32A/ 230VAC 0.3A/ 277VAC0.64A/ 115VAC 0.32A/ 230VAC 0.3A/ 277VAC0.64A/ 115VAC 0.32A/ 230VAC 0.3A/ 277VAC0.64A/ 115VAC 0.32A/ 230VAC 0.3A/ 277VAC
INRUSH CURRENT(Typ.)COLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410COLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410COLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410COLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410
MAX. No. of PSUs on 16A
CIRCUIT BREAKER
9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VAC9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VAC9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VAC9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VACCOLD START 55A(t =265 s measured at 50% I ) at 230VAC; width peak Per NEMA410
LEAKAGE CURRENT<0.75mA/ 277VAC<0.75mA/ 277VAC<0.75mA/ 277VAC<0.75mA/ 277VAC