HVG-65 series
65W Constant Voltage + Constant Current LED Driver
buy online NOW
Application:
Features
Wide input range 180 ~ 528VAC
Constant Voltage + Constant current mode ouput
Metal housing design with class 1 design
Built-in active PFC function
Class 2 power unit
IP67 / IP65 design for indoor or outdoor installations
Function options: output adjustable via potentiometer
3 in 1 dimming (dim-to-off)
Timer dimming
Typical lifetime > 50000 hours
5 year warranty
HVG-65 series
MODEL | HVG-65-12 | HVG-65-15 | HVG-65-20 | |
---|---|---|---|---|
OUTPUT | DC VOLTAGE | 12V | 15V | 20V |
CONSTANT CURRENT REGION | 7.2 ~12V | 9 ~ 15V | 12 ~ 20V | |
RATED CURRENT | 5A | 4.3A | 3.25A | |
RATED POWER | 60W | 64.5W | 65W | |
RIPPLE & NOISE (max.) | 120mVp-p | 150mVp-p | 150mVp-p | |
VOLTAGEADJ. RANGE = Adjustable forA-Type only (via the built-in potentiometer) | 10.8 ~ 13.5V | 13.5 ~ 17V | 17 ~ 22V | |
CURRENT ADJ. RANGE - Adjustable forA-Type only (via the built-in potentiometer) | 3 ~ 5A | 2.58 ~ 4.3A | 1.95 ~ 3.25A | |
VOLTAGE TOLERANCE | ±2.0% | ±2.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±1.5% | ±1.5% | ±0.5% | |
SET UP TIME | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | |
HOLD UP TIME (Typ.) | 16ms / 347VAC 30ms / 480VAC | 16ms / 347VAC 30ms / 480VAC | 16ms / 347VAC 30ms / 480VAC | |
INPUT | VOLTAGE RANGE | 180 ~ 528VAC 254VDC ~ 747VDC | 180 ~ 528VAC 254VDC ~ 747VDC | 180 ~ 528VAC 254VDC ~ 747VDC |
FREQUENCY RANGE | 47 ~ 63Hz | 47 ~ 63Hz | 47 ~ 63Hz | |
POWER FACTOR (Typ.) | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | |
TOTAL HARMONIC DISTORTION | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | |
EFFICIENCY (Typ.) | 86.5% | 87.5% | 88.5% | |
AC CURRENT (Typ.) | 0.22A/ 347VAC 0.18A/ 480VAC | 0.22A/ 347VAC 0.18A/ 480VAC | 0.22A/ 347VAC 0.18A/ 480VAC | |
INRUSH CURRENT(Typ.) | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | |
MAX. No. of PSUs on 16A CIRCUIT BREAKER | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | |
LEAKAGE CURRENT | <0.75mA/ 480VAC | <0.75mA/ 480VAC | <0.75mA/ 480VAC | |
Specs Sheet |
HVG-65 series
MODEL | HVG-65-24 | HVG-65-30 | HVG-65-36 | |
---|---|---|---|---|
OUTPUT | DC VOLTAGE | 24V | 30V | 36V |
CONSTANT CURRENT REGION | 14.4 ~ 24V | 18 ~ 30V | 21.6 ~ 36V | |
RATED CURRENT | 2.71A | 2.17A | 1.81A | |
RATED POWER | 65W | 65.1W | 65.2W | |
RIPPLE & NOISE (max.) | 150mVp-p | 200mVp-p | 200mVp-p | |
VOLTAGEADJ. RANGE = Adjustable forA-Type only (via the built-in potentiometer) | 22 ~ 27V | 27 ~ 33V | 33 ~ 40V | |
CURRENT ADJ. RANGE - Adjustable forA-Type only (via the built-in potentiometer) | 1.62 ~ 2.71A | 1.3 ~ 2.17A | 1.08 ~ 1.81A | |
VOLTAGE TOLERANCE | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±0.5% | ±0.5% | ±0.5% | |
SET UP TIME | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | |
HOLD UP TIME (Typ.) | 16ms / 347VAC 30ms / 480VAC | 16ms / 347VAC 30ms / 480VAC | 16ms / 347VAC 30ms / 480VAC | |
INPUT | VOLTAGE RANGE | 180 ~ 528VAC 254VDC ~ 747VDC | 180 ~ 528VAC 254VDC ~ 747VDC | 180 ~ 528VAC 254VDC ~ 747VDC |
FREQUENCY RANGE | 47 ~ 63Hz | 47 ~ 63Hz | 47 ~ 63Hz | |
POWER FACTOR (Typ.) | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | |
TOTAL HARMONIC DISTORTION | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | |
EFFICIENCY (Typ.) | 89% | 89% | 89.5% | |
AC CURRENT (Typ.) | 0.22A/ 347VAC 0.18A/ 480VAC | 0.22A/ 347VAC 0.18A/ 480VAC | 0.22A/ 347VAC 0.18A/ 480VAC | |
INRUSH CURRENT(Typ.) | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | |
MAX. No. of PSUs on 16A CIRCUIT BREAKER | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | |
LEAKAGE CURRENT | <0.75mA/ 480VAC | <0.75mA/ 480VAC | <0.75mA/ 480VAC | |
Specs Sheet |
HVG-65 series
MODEL | HVG-65-42 | HVG-65-48 | HVG-65-54 | |
---|---|---|---|---|
OUTPUT | DC VOLTAGE | 42V | 48V | 54V |
CONSTANT CURRENT REGION | 25.2 ~ 42V | 28.8 ~ 48V | 32.4 ~ 54V | |
RATED CURRENT | 1.55A | 1.36A | 1.21A | |
RATED POWER | 65.1W | 65.3W | 65.3W | |
RIPPLE & NOISE (max.) | 300mVp-p | 300mVp-p | 300mVp-p | |
VOLTAGEADJ. RANGE = Adjustable forA-Type only (via the built-in potentiometer) | 38 ~ 46V | 43 ~ 53V | 49 ~ 58V | |
CURRENT ADJ. RANGE - Adjustable forA-Type only (via the built-in potentiometer) | 0.93 ~ 1.55A | 0.81 ~ 1.36A | 0.72 ~ 1.21A | |
VOLTAGE TOLERANCE | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±0.5% | ±0.5% | ±0.5% | |
SET UP TIME | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | 500ms, 80ms /230VAC 400ms, 80ms /347VAC, 480VAC | |
HOLD UP TIME (Typ.) | 16ms / 347VAC 30ms / 480VAC | 16ms / 347VAC 30ms / 480VAC | 16ms / 347VAC 30ms / 480VAC | |
INPUT | VOLTAGE RANGE | 180 ~ 528VAC 254VDC ~ 747VDC | 180 ~ 528VAC 254VDC ~ 747VDC | 180 ~ 528VAC 254VDC ~ 747VDC |
FREQUENCY RANGE | 47 ~ 63Hz | 47 ~ 63Hz | 47 ~ 63Hz | |
POWER FACTOR (Typ.) | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | PF>=0.98/230VAC, PF>=0.97/277VAC, PF>=0.97/347VAC, PF 0.93/480VAC @full load | |
TOTAL HARMONIC DISTORTION | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | THD< 20%(@ load>=60%/230VAC, 277VAC, 347VAC; @ load>=75%/480VAC) | |
EFFICIENCY (Typ.) | 89.5% | 90% | 90% | |
AC CURRENT (Typ.) | 0.22A/ 347VAC 0.18A/ 480VAC | 0.22A/ 347VAC 0.18A/ 480VAC | 0.22A/ 347VAC 0.18A/ 480VAC | |
INRUSH CURRENT(Typ.) | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | COLD START 25A(t =420 s measured at 50% I ) at 480VAC; width peak Per NEMA410 | |
MAX. No. of PSUs on 16A CIRCUIT BREAKER | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | 12 units (circuit breaker of type B) / 20 units (circuit breaker of type C) at 480VAC | |
LEAKAGE CURRENT | <0.75mA/ 480VAC | <0.75mA/ 480VAC | <0.75mA/ 480VAC | |
Specs Sheet |